PRODUCT OVERVIEW : Motor protection relay (MPCB) 17-23 A (PTNO : GV2ME32)
Enter Your Keyword or Product Code or Part Number Here
Enter Your Keyword or Product Code or Part Number Here
 
                                # PRODUCT NAME
Motor protection relay (MPCB) 17-23 A (PTNO : GV2ME32)
# PART/PRODUCT NO
GV2ME32
# BRAND
Schneider Electric
# CATEGORY
MOTOR PROTECTION
| Range | TeSys Deca | 
|---|---|
| Product name | TeSys GV2 TeSys Deca | 
| product or component type | Motor circuit breaker | 
| device short name | GV2ME | 
| Device application | Motor protection | 
| Trip unit technology | Thermal-magnetic | 
| Poles description | 3P | 
|---|---|
| Network type | AC | 
| Utilisation category | Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 | 
| Network frequency | 50/60 Hz conforming to IEC 60947-4-1 | 
| Fixing mode | 35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate) | 
| Motor power kW | 15 kW at 400/415 V AC 50/60 Hz 18.5 kW at 500 V AC 50/60 Hz 22 kW at 690 V AC 50/60 Hz | 
| Breaking capacity | 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| Control type | Push-button | 
| [In] rated current | 32 A | 
| Thermal protection adjustment range | 24…32 A conforming to IEC 60947-4-1 | 
| Magnetic tripping current | 416 A | 
| [Ith] conventional free air thermal current | 32 A conforming to IEC 60947-4-1 | 
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 | 
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 | 
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 | 
| Suitability for isolation | Yes conforming to IEC 60947-1 § 7-1-6 | 
| Power dissipation per pole | 2.5 W | 
| Mechanical durability | 100000 cycles | 
| Electrical durability | 100000 cycles for AC-3 at 415 V In | 
| Rated duty | Continuous conforming to IEC 60947-4-1 | 
| Tightening torque | 1.7 N.m - on screw clamp terminal | 
| Width | 45 mm | 
| Height | 89 mm | 
| Depth | 78.5 mm | 
| Net weight | 0.26 kg | 
| Colour | Dark grey | 
| Standards | EN/IEC 60947-2 EN/IEC 60947-4-1 | 
|---|---|
| Product certifications | CCC UL CSA EAC ATEX LROS (Lloyds register of shipping) BV RINA DNV-GL UKCA | 
| IK degree of protection | IK04 | 
| IP degree of protection | IP20 conforming to IEC 60529 | 
| Climatic withstand | Conforming to IACS E10 | 
| Ambient air temperature for storage | -40…80 °C | 
| Fire resistance | 960 °C conforming to IEC 60695-2-11 | 
| Ambient air temperature for operation | -20…60 °C | 
| Mechanical robustness | Shocks: 30 Gn for 11 ms Vibrations: 5 Gn, 5...150 Hz | 
| Operating altitude | 2000 m |