PRODUCT OVERVIEW : Motor protection relay (MPCB) 0.1...0.16 A (PTNO : GV2ME01)

Enter Your Keyword or Product Code or Part Number Here

Motor protection relay (MPCB) 0.1...0.16 A (PTNO : GV2ME01)

# PRODUCT NAME

Motor protection relay (MPCB) 0.1...0.16 A (PTNO : GV2ME01)

# PART/PRODUCT NO

GV2ME01

# BRAND

Schneider Electric

# CATEGORY

MOTOR PROTECTION

Main
RangeTeSys Deca
Product nameTeSys GV2
TeSys Deca
Product or Component TypeMotor circuit breaker
device short nameGV2ME
Device ApplicationMotor protection
Trip unit technologyThermal-magnetic

Complementary
Poles description3P
Network typeAC
Utilisation categoryCategory A IEC 60947-2
AC-3 IEC 60947-4-1
Network frequency50/60 Hz IEC 60947-4-1
Fixing mode35 mm symmetrical DIN rail clipped
Panel screwed with adaptor plate)
Breaking capacity100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
100 kA Icu 440 V AC 50/60 Hz IEC 60947-2
100 kA Icu 500 V AC 50/60 Hz IEC 60947-2
100 kA Icu 690 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 % 230/240 V AC 50/60 Hz IEC 60947-2
100 % 400/415 V AC 50/60 Hz IEC 60947-2
100 % 440 V AC 50/60 Hz IEC 60947-2
100 % 500 V AC 50/60 Hz IEC 60947-2
100 % 690 V AC 50/60 Hz IEC 60947-2
Control TypePush-button
Line Rated Current0.16 A
Thermal protection adjustment range0.1…0.16 A IEC 60947-4-1
Magnetic tripping current1.5 A
[Ith] conventional free air thermal current0.16 A IEC 60947-4-1
[Ue] rated operational voltage690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage690 V AC 50/60 Hz IEC 60947-2
[Uimp] rated impulse withstand voltage6 kV IEC 60947-2
Phase failure sensitivityYes IEC 60947-4-1
Suitability for isolationYes IEC 60947-1 § 7-1-6
Power dissipation per pole2.5 W
Mechanical durability100000 cycles
Electrical durability100000 cycles AC-3 415 V In
Rated dutyContinuous IEC 60947-4-1
Tightening torque15.05 lbf.in (1.7 N.m) screw clamp terminal
Width1.77 in (45 mm)
Height3.50 in (89 mm)
Depth3.09 in (78.5 mm)
Net Weight0.57 lb(US) (0.26 kg)
colorDark grey

Environment
StandardsEN/IEC 60947-2
EN/IEC 60947-4-1
Product CertificationsCCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCA
IK degree of protectionIK04
IP degree of protectionIP20 IEC 60529
Climatic withstandIACS E10
Ambient Air Temperature for Storage-40…176 °F (-40…80 °C)
Fire resistance1760 °F (960 °C) IEC 60695-2-11
Ambient air temperature for operation-4…140 °F (-20…60 °C)
Mechanical robustnessShocks 30 Gn for 11 ms
Vibrations 5 Gn, 5...150 Hz
Operating altitude6561.68 ft (2000 m)