PRODUCT OVERVIEW : 12A, 3P, 1N/O+1N/C, 48Vac Coil(PTNO : LC1D12E7)

Enter Your Keyword or Product Code or Part Number Here

12A, 3P, 1N/O+1N/C, 48Vac Coil(PTNO : LC1D12E7)

# PRODUCT NAME

12A, 3P, 1N/O+1N/C, 48Vac Coil(PTNO : LC1D12E7)

# PART/PRODUCT NO

LC1D12E7

# BRAND

Schneider Electric

# CATEGORY

POWER CONTACTOR

Main
Range of ProductTeSys Deca
Product or Component TypeContactor
device short nameLC1D
contactor applicationMotor control
Resistive load
Utilisation categoryAC-4
AC-1
AC-3
AC-3e
Poles description3P
[Ue] rated operational voltagePower circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current25 A 140 °F (60 °C)) <= 440 V AC AC-1 power circuit
12 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit
12 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit
[Uc] control circuit voltage48 V AC 50/60 Hz

Complementary
Motor power kW3 kW 220...230 V AC 50/60 Hz AC-3)
5.5 kW 380...400 V AC 50/60 Hz AC-3)
5.5 kW 415...440 V AC 50/60 Hz AC-3)
7.5 kW 500 V AC 50/60 Hz AC-3)
7.5 kW 660...690 V AC 50/60 Hz AC-3)
3.7 kW 400 V AC 50/60 Hz AC-4)
3 kW 220...230 V AC 50/60 Hz AC-3e)
5.5 kW 380...400 V AC 50/60 Hz AC-3e)
5.5 kW 415...440 V AC 50/60 Hz AC-3e)
7.5 kW 500 V AC 50/60 Hz AC-3e)
7.5 kW 660...690 V AC 50/60 Hz AC-3e)
Maximum Horse Power Rating0.5 hp 115 V at AC 50/60 Hz for 1 phase
2 hp 230/240 V at AC 50/60 Hz for 1 phase
3 hp 200/208 V at AC 50/60 Hz for 3 phase
3 hp 230/240 V at AC 50/60 Hz for 3 phase
7.5 hp 460/480 V at AC 50/60 Hz for 3 phase
10 hp 575/600 V at AC 50/60 Hz for 3 phase
Compatibility codeLC1D
Pole contact composition3 NO
Contact compatibilityM2
Protective coverWith
[Ith] conventional free air thermal current25 A 140 °F (60 °C) power circuit
10 A 140 °F (60 °C) signalling circuit
Irms rated making capacity250 A 440 V power circuit IEC 60947
140 A AC signalling circuit IEC 60947-5-1
250 A DC signalling circuit IEC 60947-5-1
Rated breaking capacity250 A 440 V power circuit IEC 60947
[Icw] rated short-time withstand current105 A 104 °F (40 °C) - 10 s power circuit
210 A 104 °F (40 °C) - 1 s power circuit
30 A 104 °F (40 °C) - 10 min power circuit
61 A 104 °F (40 °C) - 1 min power circuit
100 A - 1 s signalling circuit
120 A - 500 ms signalling circuit
140 A - 100 ms signalling circuit
Associated fuse rating10 A gG signalling circuit IEC 60947-5-1
40 A gG <= 690 V type 1 power circuit
25 A gG <= 690 V type 2 power circuit
Average impedance2.5 mOhm - Ith 25 A 50 Hz power circuit
Power dissipation per pole0.36 W AC-3
1.56 W AC-1
0.36 W AC-3e
[Ui] rated insulation voltagePower circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability15 Mcycles
Electrical durability2 Mcycles 12 A AC-3 <= 440 V
0.8 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 12 A AC-3e <= 440 V
Control circuit typeAC 50/60 Hz standard
Coil technologyWithout built-in suppressor module
Control circuit voltage limits0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA70 VA 60 Hz 0.75 68 °F (20 °C))
70 VA 50 Hz 0.75 68 °F (20 °C))
Hold-in power consumption in VA7.5 VA 60 Hz 0.3 68 °F (20 °C))
7 VA 50 Hz 0.3 68 °F (20 °C))
Heat dissipation2…3 W 50/60 Hz
Operating time12...22 ms closing
4...19 ms opening
Maximum operating rate3600 cyc/h 140 °F (60 °C)
Connections - terminalsPower circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Power circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Power circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Power circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) flexible without cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) flexible with cable end
Control circuit screw clamp terminals 2 0.00…0.00 in² (1…2.5 mm²) flexible with cable end
Control circuit screw clamp terminals 1 0.00…0.01 in² (1…4 mm²) solid without cable end
Control circuit screw clamp terminals 2 0.00…0.01 in² (1…4 mm²) solid without cable end
Tightening torquePower circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typeMechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency25...400 Hz
Minimum switching voltage17 V signalling circuit
Minimum switching current5 mA signalling circuit
Insulation resistance> 10 MOhm signalling circuit
Non-overlap time1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting SupportRail
Plate

Environment
StandardsCSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product CertificationsLROS (Lloyds register of shipping)
DNV
BV
RINA
GOST
GL
CSA
CCC
UL
UKCA
IP degree of protectionIP20 front face IEC 60529
Protective treatmentTHIEC 60068-2-30
Climatic withstandIACS E10 exposure to damp heat
IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Operating altitude0...9842.52 ft (0...3000 m)
Fire resistance1562 °F (850 °C) IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Mechanical robustnessVibrations contactor open 2 Gn, 5...300 Hz)
Vibrations contactor closed 4 Gn, 5...300 Hz)
Shocks contactor open 10 Gn for 11 ms)
Shocks contactor closed 15 Gn for 11 ms)
Height3.03 in (77 mm)
Width1.77 in (45 mm)
Depth3.39 in (86 mm)
Net Weight0.72 lb(US) (0.325 kg)